Headline
CVE-2023-1150: VDE-2023-005 | CERT@VDE
Uncontrolled resource consumption in Series WAGO 750-3x/-8x products may allow an unauthenticated remote attacker to DoS the MODBUS server with specially crafted packets.
2023-06-25 08:00 (CEST) VDE-2023-005
WAGO: Series 750-3x/-8x prone to MODBUS server DoS
Share: Email | Twitter
Published
2023-06-25 08:00 (CEST)
Last update
2023-06-23 07:03 (CEST)
Vendor(s)
WAGO GmbH & Co. KG
Summary
An unauthenticated attacker with network access to port 502/TCP of the target device can cause a denial-of-service condition by sending multiple specially crafted packets. The MODBUS server does not properly release memory resources that were reserved for incomplete connection attempts by MODBUS clients. This could allow a remote attacker to generate a denial of service condition on devices that incorporate a vulnerable version of the MODBUS server.
CVE ID
Last Update:
June 14, 2023, 4:44 p.m.
Severity
Weakness
Uncontrolled Resource Consumption (CWE-400)
Summary
Uncontrolled resource consumption in Series WAGO 750-3x/-8x products may allow an unauthenticated remote attacker to DoS the MODBUS server with specially crafted packets.
Details
Impact
Abusing this vulnerability an attacker can crash an affected product, which fully prevents the product to work as intended. After a complete restart the component works as expected.
Solution
Mitigation
In case no MODBUS communication is needed the MODBUS-Server should be deactivated in the product settings of the web-based management.
As general security measures WAGO strongly recommends:
- Use general security best practices to protect systems from local and network attacks.
- Do not allow direct access to the device from untrusted networks.
- Update to the latest firmware according to the table in chapter solutions.
- Industrial control systems (ICS) should not be directly accessible from the Internet, but should be protected by consistently applying the defense-in-depth strategy. The BSI provides general information on securing ICS in the ICS Compendium (www.bsi.bund.de/SharedDocs/Downloads/EN/BSI/ICS/ICS-Security_compendium.pdf).
Remediation
We recommend all effected users to update to the firmware version listed below:
Series WAGO 750-3x/-8x
Article Number
Fixed in Firmware Version
750-332
FW11 after BACnet certification
750-362/xxx-xxx
FW11 Q3/2023
750-363/xxx-xxx
FW11 Q3/2023
750-364/xxx-xxx
FW11 Q3/2023
750-365/xxx-xxx
FW11 Q3/2023
750-823
FW11 Q3/2023
750-832/xxx-xxx
FW11 after BACnet certification
750-862
FW11 Q1/2023
750-890/xxx-xxx
FW11 Q3/2023
750-891
FW11 Q3/2023
750-893
FW11 Q3/2023
Reported by
WAGO thanks Roman Ezhov from Kaspersky for reporting.
CERT@VDE coordinated with WAGO.