Headline
Siemens RUGGEDCOM and SCALANCE M-800/S615 Family
As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global). View CSAF
- EXECUTIVE SUMMARY CVSS v3 9.1 ATTENTION: Exploitable remotely/low attack complexity Vendor: Siemens Equipment: SCALANCE M-800/S615 Family Vulnerabilities: Improper Validation of Specified Quantity in Input, Use of Hard-coded Cryptographic Key, Use of Weak Hash, Forced Browsing, Uncontrolled Resource Consumption, Unchecked Return Value, Injection, Unsynchronized Access to Shared Data in a Multithreaded Context, OS Command Injection
- RISK EVALUATION Successful exploitation of these vulnerabilities could allow an attacker to inject code or spawn a system root shell.
- TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following products of Siemens, are affected: RUGGEDCOM RM1224 LTE(4G) EU (6GK6108-4AM00-2BA2): All versions prior to V8.0 RUGGEDCOM RM1224 LTE(4G) EU (6GK6108-4AM00-2BA2): All versions RUGGEDCOM RM1224 LTE(4G) NAM (6GK6108-4AM00-2DA2): All versions prior to V8.0 RUGGEDCOM RM1224 LTE(4G) NAM (6GK6108-4AM00-2DA2): All versions SCALANCE M804PB (6GK5804-0AP00-2AA2): All versions prior to V8.0 SCALANCE M804PB (6GK5804-0AP00-2AA2): All versions SCALANCE M812-1 ADSL-Router (Annex A) (6GK5812-1AA00-2AA2): All versions prior to V8.0 SCALANCE M812-1 ADSL-Router (Annex A) (6GK5812-1AA00-2AA2): All versions SCALANCE M812-1 ADSL-Router (Annex B) (6GK5812-1BA00-2AA2): All versions prior to V8.0 SCALANCE M812-1 ADSL-Router (Annex B) (6GK5812-1BA00-2AA2): All versions SCALANCE M816-1 ADSL-Router (Annex A) (6GK5816-1AA00-2AA2): All versions prior to V8.0 SCALANCE M816-1 ADSL-Router (Annex A) (6GK5816-1AA00-2AA2): All versions SCALANCE M816-1 ADSL-Router (Annex B) (6GK5816-1BA00-2AA2): All versions prior to V8.0 SCALANCE M816-1 ADSL-Router (Annex B) (6GK5816-1BA00-2AA2): All versions SCALANCE M826-2 SHDSL-Router (6GK5826-2AB00-2AB2): All versions prior to V8.0 SCALANCE M826-2 SHDSL-Router (6GK5826-2AB00-2AB2): All versions SCALANCE M874-2 (6GK5874-2AA00-2AA2): All versions prior to V8.0 SCALANCE M874-2 (6GK5874-2AA00-2AA2): All versions SCALANCE M874-3 (6GK5874-3AA00-2AA2): All versions prior to V8.0 SCALANCE M874-3 (6GK5874-3AA00-2AA2): All versions SCALANCE M876-3 (EVDO) (6GK5876-3AA02-2BA2): All versions prior to V8.0 SCALANCE M876-3 (EVDO) (6GK5876-3AA02-2BA2): All versions SCALANCE M876-3 (ROK) (6GK5876-3AA02-2EA2): All versions prior to V8.0 SCALANCE M876-3 (ROK) (6GK5876-3AA02-2EA2): All versions SCALANCE M876-4 (6GK5876-4AA10-2BA2): All versions prior to V8.0 SCALANCE M876-4 (6GK5876-4AA10-2BA2): All versions SCALANCE M876-4 (EU) (6GK5876-4AA00-2BA2): All versions prior to V8.0 SCALANCE M876-4 (EU) (6GK5876-4AA00-2BA2): All versions SCALANCE M876-4 (NAM) (6GK5876-4AA00-2DA2): All versions prior to V8.0 SCALANCE M876-4 (NAM) (6GK5876-4AA00-2DA2): All versions SCALANCE MUM853-1 (EU) (6GK5853-2EA00-2DA1): All versions prior to V8.0 SCALANCE MUM853-1 (EU) (6GK5853-2EA00-2DA1): All versions SCALANCE MUM856-1 (EU) (6GK5856-2EA00-3DA1): All versions prior to V8.0 SCALANCE MUM856-1 (EU) (6GK5856-2EA00-3DA1): All versions SCALANCE MUM856-1 (RoW) (6GK5856-2EA00-3AA1): All versions prior to V8.0 SCALANCE MUM856-1 (RoW) (6GK5856-2EA00-3AA1): All versions SCALANCE S615 (6GK5615-0AA00-2AA2): All versions prior to V8.0 SCALANCE S615 (6GK5615-0AA00-2AA2): All versions SCALANCE S615 EEC (6GK5615-0AA01-2AA2): All versions prior to V8.0 SCALANCE S615 EEC (6GK5615-0AA01-2AA2): All versions 3.2 Vulnerability Overview 3.2.1 IMPROPER VALIDATION OF SPECIFIED QUANTITY IN INPUT CWE-1284 Affected devices do not check the TFTP blocksize correctly. This could allow an authenticated attacker to read from an uninitialized buffer that potentially contains previously allocated data. CVE-2022-46143 has been assigned to this vulnerability. A CVSS v3 base score of 2.7 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:L/I:N/A:N). 3.2.2 USE OF HARD-CODED CRYPTOGRAPHIC KEY CWE-321 Affected devices use a hard-coded key to obfuscate the configuration backup that an administrator can export from the device. This could allow an authenticated attacker with administrative privileges or an attacker that obtains a configuration backup to extract configuration information from the exported file. CVE-2023-44318 has been assigned to this vulnerability. A CVSS v3 base score of 4.9 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:N/A:N). 3.2.3 USE OF WEAK HASH CWE-328 Affected devices use a weak checksum algorithm to protect the configuration backup that an administrator can export from the device. This could allow an authenticated attacker with administrative privileges or an attacker that tricks a legitimate administrator to upload a modified configuration file to change the configuration of an affected device. CVE-2023-44319 has been assigned to this vulnerability. A CVSS v3 base score of 4.9 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:N/I:H/A:N). 3.2.4 DIRECT REQUEST (‘FORCED BROWSING’) CWE-425 Affected devices do not properly validate the authentication when performing certain modifications in the web interface allowing an authenticated attacker to influence the user interface configured by an administrator. CVE-2023-44320 has been assigned to this vulnerability. A CVSS v3 base score of 4.3 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:L/A:N). 3.2.5 UNCONTROLLED RESOURCE CONSUMPTION CWE-400 Affected devices do not properly validate the length of inputs when performing certain configuration changes in the web interface allowing an authenticated attacker to cause a denial of service condition. The device needs to be restarted for the web interface to become available again. CVE-2023-44321 has been assigned to this vulnerability. A CVSS v3 base score of 2.7 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:N/I:N/A:L). 3.2.6 UNCHECKED RETURN VALUE CWE-252 Affected devices can be configured to send emails when certain events occur on the device. When presented with an invalid response from the SMTP server, the device triggers an error that disrupts email sending. An attacker with access to the network can use this to do disable notification of users when certain events occur. CVE-2023-44322 has been assigned to this vulnerability. A CVSS v3 base score of 3.7 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:L). 3.2.7 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS IN OUTPUT USED BY A DOWNSTREAM COMPONENT (‘INJECTION’) CWE-74 Affected devices do not properly sanitize an input field. This could allow an authenticated remote attacker with administrative privileges to inject code or spawn a system root shell. Follow-up of CVE-2022-36323. CVE-2023-44373 has been assigned to this vulnerability. A CVSS v3 base score of 9.1 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:C/C:H/I:H/A:H). 3.2.8 UNSYNCHRONIZED ACCESS TO SHARED DATA IN A MULTITHREADED CONTEXT CWE-567 Affected devices allow to change the password, but insufficiently check which password is to be changed. With this an authenticated attacker could, under certain conditions, be able to change the password of another, potential admin user allowing her to escalate her privileges. CVE-2023-44374 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:N). 3.2.9 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN OS COMMAND (‘OS COMMAND INJECTION’) CWE-78 An improper neutralization of special elements used in an OS command with root privileges vulnerability exists in the handling of the DDNS configuration. This could allow malicious local administrators to issue commands on system level after a successful IP address update. CVE-2023-49691 has been assigned to this vulnerability. A CVSS v3 base score of 7.2 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H). 3.3 BACKGROUND CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing COUNTRIES/AREAS DEPLOYED: Worldwide COMPANY HEADQUARTERS LOCATION: Germany 3.4 RESEARCHER Siemens reported these vulnerabilities to CISA.
- MITIGATIONS Siemens has released a new version for SCALANCE M-800 / S615 and recommends users update to the latest version. Siemens recommends countermeasures for products where fixes are not, or not yet available: For CVE-2022-46143, CVE-2023-44319, CVE-2023-44322, CVE-2023-44373, CVE-2023-44374, CVE-2023-49691: Update to V8.0 or [later version https://support.industry.siemens.com/cs/ww/en/view/109826372/] For CVE-2023-44318, CVE-2023-44320, CVE-2023-44321: Currently no fix is planned, practice general security measures detailed below. As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals. Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage. For more information see the associated Siemens security advisory SSA-180704 in HTML and CSAF. CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as: Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolating them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. CISA also recommends users take the following measures to protect themselves from social engineering attacks: Do not click web links or open attachments in unsolicited email messages. Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams. Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks. No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.
- UPDATE HISTORY December 14, 2023: Initial Publication