Security
Headlines
HeadlinesLatestCVEs

Headline

Rockwell Automation FactoryTalk ThinManager

View CSAF

  1. EXECUTIVE SUMMARY CVSS v4 9.3 ATTENTION: Exploitable remotely/low attack complexity Vendor: Rockwell Automation Equipment: FactoryTalk ThinManager Vulnerabilities: Missing Authentication For Critical Function, Out-of-Bounds Read
  2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow an attacker to send crafted messages to the device resulting in database manipulation or a denial-of-service condition.
  3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following Rockwell Automation FactoryTalk product versions are affected: ThinManager: Versions 11.2.0 to 11.2.9 ThinManager: Versions 12.0.0 to 12.0.7 ThinManager: Versions 12.1.0 to 12.1.8 ThinManager: Versions 13.0.0 to 13.0.5 ThinManager: Versions 13.1.0 to 13.1.3 ThinManager: Versions 13.2.0 to 13.2.2 ThinManager: Version 14.0.0 3.2 Vulnerability Overview 3.2.1 MISSING AUTHENTICATION FOR CRITICAL FUNCTION CWE-306 An authentication vulnerability exists in the affected product. The vulnerability could allow a threat actor with network access to send crafted messages to the device, potentially resulting in database manipulation. CVE-2024-10386 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H). A CVSS v4 score has also been calculated for CVE-2024-10386. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N). 3.2.2 OUT-OF-BOUNDS READ CWE-125 A denial-of-service vulnerability exists in the affected product. The vulnerability could allow a threat actor with network access to send crafted messages to the device, resulting in a denial-of-service condition. CVE-2024-10387 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H). A CVSS v4 score has also been calculated for CVE-2024-10387. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N). 3.3 BACKGROUND CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing COUNTRIES/AREAS DEPLOYED: Worldwide COMPANY HEADQUARTERS LOCATION: United States 3.4 RESEARCHER Tenable Network Security reported these vulnerabilities to Rockwell Automation.
  4. MITIGATIONS Rockwell Automation has provided a fix for the affected versions on the FactoryTalk ThinManager download site. Rockwell Automation encourages users of the affected software to apply these risk mitigations if possible. Implement network hardening for ThinManager Device(s) by limiting communications to TCP 2031 to only the devices that need connection to the ThinManager. For information on how to mitigate security risks on industrial automation control systems, users are encouraged to implement Rockwell Automation’s suggested security best practices to minimize the risk of the vulnerability. For more information, see Rockwell Automation’s security bulletin. CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as: Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolating them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.
  5. UPDATE HISTORY October 31, 2024: Initial Publication
us-cert
#vulnerability#web#dos#auth

us-cert: Latest News

Automated Logic WebCTRL Premium Server