Security
Headlines
HeadlinesLatestCVEs

Headline

Siemens SINUMERIK ONE, SINUMERIK 840D and SINUMERIK 828D

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global). View CSAF

  1. EXECUTIVE SUMMARY CVSS v4 9.3 ATTENTION: Low attack complexity Vendor: Siemens Equipment: SINUMERIK ONE, SINUMERIK 840D, SINUMERIK 828D Vulnerability: Incorrect Permission Assignment for Critical Resource
  2. RISK EVALUATION Successful exploitation of this vulnerability could allow an attacker to escalate their privileges in the underlying system.
  3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Siemens SINUMERIK products, an automation system, are affected: SINUMERIK 828D V4: All versions SINUMERIK 828D V5: All versions prior to V5.24 SINUMERIK 840D sl V4: All versions SINUMERIK ONE: All versions prior to V6.24 3.2 Vulnerability Overview 3.2.1 INCORRECT PERMISSION ASSIGNMENT FOR CRITICAL RESOURCE CWE-732 Affected devices do not properly enforce access restrictions to scripts that are regularly executed by the system with elevated privileges. This could allow an authenticated local attacker to escalate their privileges in the underlying system. CVE-2024-41171 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H). A CVSS v4 score has also been calculated for CVE-2024-41171. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N). 3.3 BACKGROUND CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing COUNTRIES/AREAS DEPLOYED: Worldwide COMPANY HEADQUARTERS LOCATION: Germany 3.4 RESEARCHER Siemens reported this vulnerability to CISA.
  4. MITIGATIONS Siemens recommends users update products to the following versions: SINUMERIK 828D V4: Currently no fix is planned SINUMERIK 828D V5: Update to V5.24 or later version SINUMERIK 840D sl V4: Currently no fix is planned SINUMERIK ONE: Update to V6.24 or later version Updated software version can be obtained from Siemens customer support or a local partner. As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals. Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage For more information see the associated Siemens security advisory SSA-342438 in HTML and CSAF. CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as: Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolating them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. This vulnerability is not exploitable remotely.
  5. UPDATE HISTORY September 12, 2024: Initial Publication
us-cert
#vulnerability#web#perl#auth

us-cert: Latest News

Yokogawa Dual-redundant Platform for Computer (PC2CKM)