Source
us-cert
View CSAF 1. EXECUTIVE SUMMARY CVSS v3 7.5 ATTENTION: Exploitable remotely/low attack complexity Vendor: AutomationDirect Equipment: C-MORE EA9 HMI Vulnerabilities: Path Traversal, Stack-Based Buffer Overflow, Plaintext Storage of a Password 2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow an attacker to exploit a remote device and inject malicious code on the panel. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of C-MORE EA9 HMI, a display system used for interfacing with controllers, are affected: C-MORE EA9 HMI EA9-T6CL: Version 6.77 and prior C-MORE EA9 HMI EA9-T7CL: Version 6.77 and prior C-MORE EA9 HMI EA0-T7CL-R: Version 6.77 and prior C-MORE EA9 HMI EA9-T8CL: Version 6.77 and prior C-MORE EA9 HMI EA9-T10CL: Version 6.77 and prior C-MORE EA9 HMI EA9-T10WCL: Version 6.77 and prior C-MORE EA9 HMI EA9-T12CL: Version 6.77 and prior C-MORE EA9 HMI EA9-T15CL: Version 6.77 and prior C-MORE EA9 HMI EA9-T15CL-R: Version 6.77 and prior C-...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 6.9 ATTENTION: Exploitable remotely/low attack complexity Vendor: Rockwell Automation Equipment: FactoryTalk View ME Vulnerability: Cross-site Scripting 2. RISK EVALUATION Successful exploitation of this vulnerability could lead to the loss of view or control of the PanelView product. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of FactoryTalk View ME, an HMI software application, are affected: FactoryTalk View ME: prior to v14 3.2 Vulnerability Overview 3.2.1 Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting') CWE-79 A vulnerability exists in the affected product that allows a malicious user to restart the PanelView Plus 7 terminal remotely without security protections. If the vulnerability is exploited, it could lead to the loss of view or control of the PanelView product. CVE-2024-21914 has been assigned to this vulnerability. A CVSS v3.1 base score of 5.3 has been calculated; the CVSS vecto...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 8.7 ATTENTION: Exploitable remotely/low attack complexity Vendor: Rockwell Automation Equipment: PowerFlex 527 Vulnerabilities: Improper Input Validation, Uncontrolled Resource Consumption 2. RISK EVALUATION Successful exploitation of this these vulnerabilities could crash the device and require a manual restart to recover. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS Rockwell Automation reports that the following versions of PowerFlex 527 adjustable frequency AC drives are affected: PowerFlex 527: Versions v2.001.x and later 3.2 Vulnerability Overview 3.2.1 Improper Input Validation CWE-120 A denial-of-service vulnerability exists in the PowerFlex 527 due to improper input validation in the device. If exploited, the web server will crash and need a manual restart to recover it. CVE-2024-2425 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H). A ...
View CSAF 1. EXECUTIVE SUMMARY CVSS v3 7.8 ATTENTION: low attack complexity Vendor: Rockwell Automation Equipment: Arena Simulation Software Vulnerabilities: Out-of-bounds Write, Heap-based Buffer Overflow, Improper Restriction of Operations within the Bounds of a Memory Buffer, Use After Free, Access of Uninitialized Pointer, Out-of-bounds Read 2. RISK EVALUATION Successful exploitation of these vulnerabilities could crash the application or allow an attacker to run harmful code on the system. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS Rockwell Automation reports that the following versions of Arena Simulation Software are affected: Arena Simulation Software: version 16.00 3.2 Vulnerability Overview 3.2.1 Out-of-bounds Write CWE-787 An arbitrary code execution vulnerability could let a malicious user insert unauthorized code into the software. This is done by writing beyond the designated memory area, which causes an access violation. Once inside, the threat actor can run harmful code...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 7.1 ATTENTION: Exploitable remotely/low attack complexity/public exploits are available Vendor: Advantech Equipment: WebAccess/SCADA Vulnerability: SQL Injection 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an authenticated attacker to read or modify a remote database. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Advantech WebAccess/SCADA, a bowser-based SCADA software, are affected: WebAccess/SCADA: Version 9.1.5U 3.2 Vulnerability Overview 3.2.1 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN SQL COMMAND ('SQL INJECTION') CWE-89: There is a SQL Injection vulnerability in Advantech's WebAccess/SCDA software that allows an authenticated attacker to remotely inject SQL code on the database. Successful exploitation of this vulnerability could allow an attacker to read or modify data on the remote database. CVE-2024-2453 has been assigned to this vulnerability. A CVSS v3.1 base score of 6...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 8.7 ATTENTION: Exploitable remotely/low attack complexity Vendor: Franklin Fueling System Equipment: EVO 550, EVO 5000 Vulnerability: Path Traversal 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an attacker to read arbitrary files on the system. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Franklin Fueling System EVO 550 and EVO 5000, an automatic tank gauge (ATG), are affected: EVO 550: All versions prior to 2.26.3.8963 EVO 5000: All versions prior to 2.26.3.8963 3.2 Vulnerability Overview 3.2.1 PATH TRAVERSAL: '/../FILEDIR' CWE-25 Franklin Fueling System EVO 550 and EVO 5000 are vulnerable to a Path Traversal vulnerability that could allow an attacker to access sensitive files on the system. CVE-2024-2442 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N). A CVSS v4 score has been calcula...
As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). View CSAF 1. EXECUTIVE SUMMARY CVSS v4 6.1 ATTENTION: Exploitable remotely/low attack complexity Vendor: Siemens Equipment: SINEMA Remote Connect Client Vulnerability: Insertion of Sensitive Information into Externally-Accessible File or Directory 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an attacker to access sensitive information. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Siemens SINEMA Remote Connect Client, a remote management platform, are affected: SINEMA Remote Connect Client: All versions prior to V3.1 SP1 3.2 Vulnerability Overview 3.2.1 INSERTION OF SENSITIVE INFORMATION INTO EXTERNALLY-ACCESSIBLE FILE OR...
As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). View CSAF 1. EXECUTIVE SUMMARY CVSS v3 9.8 ATTENTION: Exploitable remotely/low attack complexity Vendor: Siemens Equipment: SIMATIC Vulnerabilities: Improper Restriction of Operations within the Bounds of a Memory Buffer, Improper Input Validation, Missing Encryption of Sensitive Data, Incorrect Permission Assignment for Critical Resource, Expected Behavior Violation, Improper Authentication, Out-of-bounds Write, Use After Free, Inadequate Encryption Strength, Use of Insufficiently Random Values, Incorrect Authorization, Improper Locking, Improper Restriction of Rendered UI Layers or Frames, Improper Privilege Management, Missing Authorization, Cleartext Storage of Sensitive ...
As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). View CSAF 1. EXECUTIVE SUMMARY CVSS v4 8.7 ATTENTION: Exploitable remotely/low attack complexity Vendor: Siemens Equipment: RUGGEDCOM APE1808 Vulnerabilities: Heap-based Buffer Overflow, External Control of File Name or Path, Improper Privilege Management, Uncontrolled Resource Consumption, Improper Certificate Validation, Out-of-bounds Write, Use of Externally-Controlled Format String 2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow an attacker to execute elevated actions, cause a denial-of-service, or execute arbitrary commands or code. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Siemens RUGGEDCOM APE1808, an applicati...
As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). View CSAF 1. EXECUTIVE SUMMARY CVSS v4 5.1 ATTENTION: Exploitable remotely/low attack complexity Vendor: Siemens Equipment: SCALANCE XB-200/XC-200/XP-200/XF-200BA/XR-300WG Family Vulnerabilities: Use of Hard-coded Cryptographic Key, Uncontrolled Resource Consumption 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an authenticated attacker to cause a denial-of-service condition or extract configuration information from a configuration backup file. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following products of Siemens, are affected: SCALANCE XB205-3 (SC, PN) (6GK5205-3BB00-2AB2): All versions SCALANCE XB205-3 (ST, E/IP) (6GK5205-3BB00-2TB2): A...