Rockwell Automation Kinetix 5500

  1. EXECUTIVE SUMMARY CVSS v3 9.4 ATTENTION: Exploitable remotely/low attack complexity Vendor: Rockwell Automation Equipment: Kinetix 5500 EtherNet/IP Servo Drive Vulnerabilities: Improper Access Control
  2. RISK EVALUATION Successful exploitation of this vulnerability could create a denial-of-service condition or allow attackers unauthorized access to the device.
  3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Kinetix 5500 EtherNet/IP Servo Drive, an industrial control router, are affected: Kinetix 5500 devices manufactured between May 2022 and January 2023: Version 7.13 3.2 VULNERABILITY OVERVIEW 3.2.1 IMPROPER ACCESS CONTROL CWE-284 Rockwell Automation Kinetix 5500 devices manufactured between May 2022 and January 2023 running Version 7.13 have telnet and file transfer protocol (FTP) ports open by default. This could allow an attacker access to the device. CVE-2023-1834 has been assigned to this vulnerability. A CVSS v3 base score of 9.4 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:H/A:H). 3.3 BACKGROUND CRITICAL INFRASTRUCTURE SECTORS: Energy, Water and Wastewater, Chemical, Critical Manufacturing COUNTRIES/AREAS DEPLOYED: Worldwide COMPANY HEADQUARTERS LOCATION: United States 3.4 RESEARCHER Rockwell Automation reported this vulnerability to CISA.
  4. MITIGATIONS Rockwell Automation recommends users upgrade the firmware of their affected devices to version 7.14 or later. Rockwell Automation recommends users follow their security best practices. CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should: Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the Internet. Locate control system networks and remote devices behind firewalls and isolate them from business networks. When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as its connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage at cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. No known public exploits specifically target this vulnerability.
us-cert
#vulnerability#web#dos#auth#telnet

us-cert: Latest News

Siemens SINEC INS