Security
Headlines
HeadlinesLatestCVEs

Headline

GE Digital CIMPLICITY

  1. EXECUTIVE SUMMARY CVSS v3 6.6 ATTENTION: Low attack complexity Vendor: GE Digital Equipment: CIMPLICITY Vulnerability: Heap-based Buffer Overflow
  2. RISK EVALUATION Successful exploitation of this vulnerability could allow an attacker to cause memory corruption issues resulting in unwanted behavior such as code execution.
  3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following GE Digital products are affected:

CIMPLICITY: All versions 3.2 VULNERABILITY OVERVIEW 3.2.1 HEAP-BASED BUFFER OVERFLOW CWE-122 All versions of GE Digital CIMPLICITY that are not adhering to SDG guidance and accepting documents from untrusted sources are vulnerable to memory corruption issues due to insufficient input validation, including issues such as out-of-bounds reads and writes, use-after-free, stack-based buffer overflows, uninitialized pointers, and a heap-based buffer overflow. Successful exploitation could allow an attacker to execute arbitrary code. CVE-2023-3463 has been assigned to this vulnerability. A CVSS v3 base score of 6.6 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:L/I:L/A:H). 3.3 BACKGROUND CRITICAL INFRASTRUCTURE SECTORS: Multiple Sectors COUNTRIES/AREAS DEPLOYED: Worldwide COMPANY HEADQUARTERS LOCATION: United States 3.4 RESEARCHER Michael Heinzl reported this vulnerability to CISA.

  1. MITIGATIONS To obtain the latest versions of GE CIMPLICITY, contact your local GE Digital representative at https://digitalsupport.ge.com/s/contactsupport. Exploit is only possible if an authenticated user with local access to the system obtains and opens a document from a malicious source so secure deployment and strong access management by users is essential. GE Digital and customers have a shared responsibility for security and users are required to adhere to the most recent Secure Deployment Guide (SDG) instructions. Please refer to GE Digital’s security bulletin for more information. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage at cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. No known public exploits specifically target this vulnerability. This vulnerability is not exploitable remotely.
us-cert
#vulnerability#web#git#buffer_overflow#auth

us-cert: Latest News

Rockwell Automation FactoryTalk ThinManager