Rockwell Automation FactoryTalk View Machine Edition

View CSAF 1. EXECUTIVE SUMMARY CVSS v3 9.8 ATTENTION: Exploitable remotely/low attack complexity Vendor: Rockwell Automation Equipment: FactoryTalk View Machine Edition Vulnerability: Improper Input Validation 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an attacker to execute code remotely with specially crafted malicious packets or by using a self-made library to bypass security checks. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following Rockwell Automation products are affected: FactoryTalk View Machine Edition: v13.0 FactoryTalk View Machine Edition: v12.0 and prior 3.2 Vulnerability Overview 3.2.1 Improper Input Validation CWE-20 FactoryTalk View Machine Edition on the PanelView Plus, improperly verifies user's input, which allows unauthenticated attacker to achieve remote code executed via crafted malicious packets. The device has the functionality, through a CIP class, to execute exported functions from libraries. There is a routine that rest...

us-cert
#vulnerability#web#mac#microsoft#intel#rce#perl#auth
Real Time Automation 460 Series

View CSAF 1. EXECUTIVE SUMMARY CVSS v3 9.4 ATTENTION: Exploitable remotely/low attack complexity/public exploits are available Vendor: Real Time Automation Equipment: 460MCBS Vulnerability: Cross-site Scripting 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an attacker to run malicious JavaScript content, resulting in cross site scripting (XSS). 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following Real Time Automation products are affected: 460 Series: Versions prior to v8.9.8 3.2 Vulnerability Overview 3.2.1 IMPROPER NEUTRALIZATION OF INPUT DURING WEB PAGE GENERATION ('CROSS-SITE SCRIPTING') CWE-79 Real Time Automation 460 Series products with versions prior to v8.9.8 are vulnerable to cross-site scripting, which could allow an attacker to run any JavaScript reference from the URL string. If this were to occur, the gateway's HTTP interface would redirect to the main page, which is index.htm. CVE-2023-4523 has been assigned to this vulnerability. A CVS...

Rockwell Automation Select Logix Communication Modules

View CSAF 1. EXECUTIVE SUMMARY CVSS v3 9.8 ATTENTION: Exploitable remotely/low attack complexity Vendor: Rockwell Automation Equipment: 1756-EN2T, 1756-EN2TK, 1756-EN2TXT, 1756-EN2TP, 1756-EN2TPK, 1756-EN2TPXT, 1756-EN2TR, 1756-EN2TRK, 1756-EN2TRXT, 1756-EN2F, 1756-EN2FK, 1756-EN3TR, 1756-EN3TRK Vulnerability: Stack-based Buffer Overflow 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an attacker to achieve remote code execution. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Rockwell Automation Logix Communication Modules, are affected: 1756-EN2T Series A: versions 5.008 and prior 1756-EN2T Series A: version 5.028 1756-EN2T Series B: versions 5.008 and prior 1756-EN2T Series B: version 5.028 1756-EN2T Series C: versions 5.008 and prior 1756-EN2T Series C: version 5.028 1756-EN2T Series D: versions 11.002 and prior 1756-EN2TK Series A: versions 5.008 and prior 1756-EN2TK Series A: version 5.028 1756-EN2TK Series B: versions 5.008 and ...

Siemens Spectrum Power 7

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global).  View CSAF 1. EXECUTIVE SUMMARY CVSS v3 8.2 ATTENTION: Low Attack Complexity Vendor: Siemens Equipment: Spectrum Power 7 Vulnerability: Incorrect Permission Assignment for Critical Resource 2. RISK EVALUATION Successful exploitation of this vulnerability could allow a local attacker to inject arbitrary code to the update script and escalate privileges. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following products of Siemens, are affected: Spectrum Power 7: versions prior to V23Q3 3.2 Vulnerability Overview 3.2.1 Incorrect Permission Assignment for Critical Resource CWE-732 The affected product assigns improper access rights to the update script. This could allow an authent...

Rockwell Automation Connected Components Workbench

View CSAF 1. EXECUTIVE SUMMARY CVSS v3 9.6 ATTENTION: Exploitable remotely/low attack complexity/public exploits are available/known public exploitation Vendor: Rockwell Automation Equipment: Connected Components Workbench Vulnerabilities: Use After Free, Out-of-bounds Write 2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow an attacker to exploit heap corruption via a crafted HTML. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Rockwell Automation Connected Components Workbench Smart Security Manager are affected: Connected Components Workbench: versions prior to R21 3.2 Vulnerability Overview 3.2.1 USE AFTER FREE CWE-416 Connected Components Workbench utilizes CefSharp version 81.3.100 that contains a use after free vulnerability in Google Chrome versions before 86.0.4240.198. If exploited, a remote threat actor could potentially perform a sandbox escape via a crafted HTML page. CVE-2020-16017 has been assigned to this vulnerability....

Omron Engineering Software

View CSAF 1. EXECUTIVE SUMMARY CVSS v3 5.5 ATTENTION: Low attack complexity Vendor: Omron Equipment: Sysmac Studio Vulnerability: Improper Authorization 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an attacker to execute arbitrary code. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Omron engineering software are affected: Sysmac Studio: version 1.54 and prior 3.2 Vulnerability Overview 3.2.1 IMPROPER AUTHORIZATION CWE-285 Omron engineering applications install executables with low privileged user "write" permissions. This could allow an attacker to alter the files to execute arbitrary code. CVE-2022-45793 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:N). 3.3 BACKGROUND CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing COUNTRIES/AREAS DEPLOYED: Worldwide COMPANY HEADQUARTERS LOCATION: Japan 3.4 RESEARCHER Reid Wightman of D...

Omron CJ/CS/CP Series

View CSAF 1. EXECUTIVE SUMMARY CVSS v3 7.5 ATTENTION: Exploitable remotely/low attack complexity Vendor: Omron Equipment: Sysmac CJ/CS/CP Series Vulnerability: Improper Control of Interaction Frequency 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an attacker to obtain sensitive information in memory. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Omron CJ/CS/CP series, programmable logic controllers, are affected: Smart Security Manager: Versions 1.4 and prior to 1.31 Smart Security Manager: Versions 1.5 and prior CJ2H-CPU ** (-EIP): version 1.4 and prior CJ2M-CPU ** : version 2.0 and prior CS1H/G-CPU ** H、CJ1G-CPU ** P: version 4.0 and prior CS1D-CPU ** H / -CPU ** P: version 1.3 and prior CS1D-CPU ** S: version 2.0 and prior CP1E-E / -N: version 1.2 and prior 3.2 Vulnerability Overview 3.2.1 IMPROPER CONTROL OF INTERACTION FREQUENCY CWE-799 Omron CJ/CS/CP series programmable logic controllers use the FINS protocol, which is vulner...

Siemens SIMATIC PCS neo Administration Console

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global).  View CSAF 1. EXECUTIVE SUMMARY CVSS v3 5.5 ATTENTION: low attack complexity Vendor: Siemens Equipment: SIMATIC PCS neo Administration Console Vulnerability: Insertion of Sensitive Information into Externally-Accessible File or Directory 2. RISK EVALUATION Successful exploitation of this vulnerability could get the credentials, and impersonate the admin user, thereby gaining admin access to other Windows systems. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS Siemens reports that the following products are affected: SIMATIC PCS neo (Administration Console): V4.0 SIMATIC PCS neo (Administration Console): V4.0 Update 1 3.2 Vulnerability Overview 3.2.1 Insertion of Sensitive Informat...

Omron Engineering Software Zip-Slip

View CSAF 1. EXECUTIVE SUMMARY CVSS v3 5.5 ATTENTION: Low attack complexity Vendor: Omron Equipment: Sysmac Studio, NX-IO Configurator Vulnerability: Path Traversal 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an attacker to overwrite files on a system. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Omron engineering software are affected: Sysmac Studio: version 1.54 and prior NX-IO Configurator: version 1.22 and prior 3.2 Vulnerability Overview 3.2.1 IMPROPER LIMITATION OF A PATHNAME TO A RESTRICTED DIRECTORY ('PATH TRAVERSAL') CWE-22 DotNetZip.Semvered before 1.11.0 is vulnerable to directory traversal, which could allow attackers to write to arbitrary files via a ../ (dot dot slash) in a Zip archive entry mishandled during extraction. This vulnerability is also known as "Zip-Slip." CVE-2018-1002205 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/U...

Siemans QMS Automotive

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global).  View CSAF 1. EXECUTIVE SUMMARY CVSS v3 8.8 ATTENTION: Exploitable remotely/low attack complexity Vendor: Siemens Equipment: QMS Automotive Vulnerabilities: Plaintext Storage of a Password, Cleartext Storage of Sensitive Information in Memory, Generation of Error Message Containing Sensitive Information, Server-generated Error Message Containing Sensitive Information, Improper Verification of Cryptographic Signature, Insecure Storage of Sensitive Information, Cleartext Transmission of Sensitive Information, Improper Access Control, Unrestricted Upload of File with Dangerous Type, Insufficient Session Expiration 2. RISK EVALUATION Successful exploitation of these vulnerabilitie...