Source
us-cert
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 9.2 ATTENTION: Exploitable remotely/low attack complexity Vendor: Rockwell Automation Equipment: FactoryTalk Vulnerability: Command Injection 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an attacker to perform unauthenticated remote code execution. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Rockwell Automation FactoryTalk View Site, are affected: FactoryTalk View Site Edition: Versions V12.0, V13.0, V14.0 3.2 Vulnerability Overview 3.2.1 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN A COMMAND ('COMMAND INJECTION') CWE-77 A remote code vulnerability exists in the affected products. The vulnerability occurs when chained with path traversal, command injection, and XSS vulnerabilities and allows for full unauthenticated remote code execution. The link in the mitigations section below contains patches to fix this issue. CVE-2024-45824 has been assigned to this vulnerability. A CVSS v3.1 ba...
As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). View CSAF 1. EXECUTIVE SUMMARY CVSS v4 9.4 ATTENTION: Exploitable remotely/low attack complexity Vendor: Siemens Equipment: SIMATIC SCADA and PCS 7 Systems Vulnerability: Execution with Unnecessary Privileges 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an unauthenticated remote attacker to execute arbitrary code with high privileges. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following Siemens products are affected: SIMATIC BATCH V9.1: All versions SIMATIC Information Server 2020: All versions SIMATIC Information Server 2022: All versions SIMATIC PCS 7 V9.1: All versions SIMATIC Process Historian 2020: All versions SIMATIC Process Historia...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 8.5 ATTENTION: Exploitable remotely/Low attack complexity Vendor: Rockwell Automation Equipment: ThinManager Vulnerability: Externally Controlled Reference to a Resource in Another Sphere 2. RISK EVALUATION Successful exploitation of this vulnerability could result in remote code execution. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Rockwell Automation ThinManager, a visualization resource manager, are affected: ThinManager: Versions V13.1.0 to 13.1.2 ThinManager: Versions V13.2.0 to 13.2.1 3.2 Vulnerability Overview 3.2.1 EXTERNALLY CONTROLLED REFERENCE TO A RESOURCE IN ANOTHER SPHERE CWE-610 Due to improper input validation, a path traversal and remote code execution vulnerability exists when the ThinManager processes a crafted POST request. If exploited, a user can install an executable file. CVE-2024-45826 has been assigned to this vulnerability. A CVSS v3 base score of 6.8 has been calculated; the CVSS vector string ...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 9.2 ATTENTION: Exploitable remotely Vendor: Rockwell Automation Equipment: FactoryTalk Batch View Vulnerability: Improper Authentication 2. RISK EVALUATION Successful exploitation of this vulnerability could result in an attacker bypassing authentication. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Rockwell Automation FactoryTalk Batch View, a manufacturing process batch solution, are affected: FactoryTalk Batch View: 2.01.00 and prior 3.2 Vulnerability Overview 3.2.1 IMPROPER AUTHENTICATION CWE-287 An authentication bypass vulnerability exists in the affected product. The vulnerability exists due to shared secrets across accounts and could allow a threat actor to impersonate a user if the threat actor is able to enumerate additional information required during authentication. CVE-2024-45823 has been assigned to this vulnerability. A CVSS v3 base score of 8.1 has been calculated; the CVSS vector string is (AV:N/AC:H/PR:N/U...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 9.3 ATTENTION: Exploitable remotely/low attack complexity/public exploits are available Vendor: Viessmann Climate Solutions SE Equipment: Vitogate 300 Vulnerabilities: Use of Hard-coded Credentials, Forced Browsing, Command Injection 2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow an attacker to achieve remote code execution. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Viessmann Climate Solutions SE Vitogate 300, a solution to connecting boilers and heat pumps to a building management system, are affected: Viessmann Vitogate 300: Versions 2.1.3.0 and prior 3.2 Vulnerability Overview 3.2.1 Use of Hard-coded Credentials CWE-798 In Viessmann Vitogate 300 versions 2.1.3.0 and prior there is a vulnerability that affects the function isValidUser of the file /cgi-bin/vitogate.cgi of the component Web Management Interface. The manipulation leads to use of hard-coded password. CVE-2023-5222 has been ...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 8.7 ATTENTION: Exploitable remotely/low attack complexity Vendor: Rockwell Automation Equipment: SequenceManager Vulnerabilities: Unquoted Search Path or Element 2. RISK EVALUATION Successful exploitation of these vulnerabilities could cause a denial-of-service condition. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of SequenceManager, a logix controller-based batch and sequencing solution, are affected: SequenceManager: Versions prior to 2.0 3.2 Vulnerability Overview 3.2.1 Unquoted Search Path or Element CWE-428 An input validation vulnerability exists in the affected products which could allow a malicious user to send malformed packets to the server and cause a denial-of-service condition. If exploited, the device would become unresponsive, and a manual restart will be required for recovery. Additionally, if exploited, there could be a loss of view for the downstream equipment sequences in the controller. Users would not be...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 8.7 ATTENTION: Exploitable remotely/low attack complexity Vendor: iniNet Solutions GmbH Equipment: SpiderControl SCADA Web Server Vulnerabilities: Unrestricted Upload of File with Dangerous Type 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an attacker to log in or execute arbitrary code. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of SpiderControl, an HMI program, are affected: SpiderControl SCADA Web Server: Versions v2.09 and prior 3.2 Vulnerability Overview 3.2.1 Unrestricted Upload of File with Dangerous Type CWE-434 SpiderControl SCADA Web Server has a vulnerability that could allow an attacker to upload specially crafted malicious files without authentication. CVE-2024-8232 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N). A CVSS v4 score has also been calculated for CVE-202...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 7.1 ATTENTION: Low attack complexity Vendor: Hughes Network Systems Equipment: WL3000 Fusion Software Vulnerabilities: Insufficiently Protected Credentials, Missing Encryption of Sensitive Data 2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow an attacker to obtain read-only access to network configuration information and terminal configuration data. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following Hughes Network Systems work streams are affected: WL3000 Fusion Software: Versions prior to 2.7.0.10 3.2 Vulnerability Overview 3.2.1 INSUFFICIENTLY PROTECTED CREDENTIALS CWE-522 Credentials to access device configuration information stored unencrypted in flash memory. These credentials would allow read-only access to network configuration information and terminal configuration data. CVE-2024-39278 has been assigned to this vulnerability. A CVSS v3.1 base score of 4.2 has been calculated; the CVSS vector string is (...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 9.3 ATTENTION: Exploitable remotely/low attack complexity/public exploits are available Vendor: LOYTEC electronics GmbH Equipment: LINX series Vulnerabilities: Cleartext Transmission of Sensitive Information, Missing Authentication for Critical Function, Cleartext Storage of Sensitive Information, Improper Access Control 2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow an attacker to disclose sensitive information or make modifications to an affected device. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following Loytec products are affected: LINX-151: All versions LINX-212: All versions LVIS-3ME12-A1: All versions LIOB-586: All versions LIOB-580 V2: All versions LIOB-588: All versions L-INX Configurator: All versions 3.2 Vulnerability Overview 3.2.1 CLEARTEXT TRANSMISSION OF SENSITIVE INFORMATION CWE-319 LOYTEC LINX-212 firmware 6.2.4, LVIS-3ME12-A1 firmware 6.2.2 and LIOB-586 firmware 6.2.3 devices send password-c...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 9.3 ATTENTION: Exploitable remotely/Low attack complexity Vendor: Rockwell Automation Equipment: ThinManager ThinServer Vulnerabilities: Improper Privilege Management, Incorrect Permission Assignment for Critical Resource, Improper Input Validation 2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow an attacker to read arbitrary files and execute arbitrary code with system privileges. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Rockwell Automation ThinManager ThinServer, a client management software, are affected: ThinManager ThinServer: Versions 11.1.0 to 11.1.7 ThinManager ThinServer: Versions 11.2.0 to 11.2.8 ThinManager ThinServer: Versions 12.0.0 to 12.0.6 ThinManager ThinServer: Versions 12.1.0 to 12.1.7 ThinManager ThinServer: Versions 13.0.0 to 13.0.4 ThinManager ThinServer: Versions 13.1.0 to 13.1.2 ThinManager ThinServer: Versions 13.2.0 to 13.2.1 3.2 Vulnerability Overview 3.2.1 Impro...