View CSAF 1. EXECUTIVE SUMMARY CVSS v4 9.3 ATTENTION: Exploitable remotely/low attack complexity Vendor: Ruijie Equipment: Reyee OS Vulnerabilities: Weak Password Recovery Mechanism for Forgotten Password, Exposure of Private Personal Information to an Unauthorized Actor, Premature Release of Resource During Expected Lifetime, Insecure Storage of Sensitive Information, Use of Weak Credentials, Improper Neutralization of Wildcards or Matching Symbols, Improper Handling of Insufficient Permissions or Privileges, Server-Side Request Forgery (SSRF), Use of Inherently Dangerous Function, Resource Leak 2. RISK EVALUATION Successful exploitation of this vulnerabilities could allow attackers to take near full control over the device. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following Ruijie product is affected: Reyee OS: Versions 2.206.x up to but not including 2.320.x 3.2 Vulnerability Overview 3.2.1 Weak Password Recovery Mechanism for Forgotten Password CWE-640 Ruijie Reyee OS version...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 9.5 ATTENTION: Exploitable remotely/low attack complexity Vendor: Schneider Electric Equipment: PowerLogic PM5500 and PowerLogic PM8ECC Vulnerabilities: Weak Password Recovery Mechanism for Forgotten Password, Improper Authentication 2. RISK EVALUATION Successful exploitation of these vulnerabilities could result in an attacker gaining escalated privileges and obtaining control of the device. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of PowerLogic PM55xx power metering devices and PowerLogic PM8ECC ethernet communication module are affected: PM5560: Versions prior to v2.7.8 PM5561: Versions prior to v10.7.3 PM5562: v2.5.4 and prior PM5563: Versions prior to v2.7.8 PM8ECC: All versions 3.2 Vulnerability Overview 3.2.1 WEAK PASSWORD RECOVERY MECHANISM FOR FORGOTTEN PASSWORD CWE-640 The affected product is vulnerable due to weak password recovery mechanisms, which may allow an attacker to gain unauthorized access and potential...
View CSAF 1. EXECUTIVE SUMMARY CVSS v3 6.1 ATTENTION: Low attack complexity Vendor: Schneider Electric Equipment: PowerLogic P5 Vulnerability: Use of a Broken or Risky Cryptographic Algorithm 2. RISK EVALUATION If an attacker has physical access to the device, it is possible to reboot the device, cause a denial of service condition, or gain full control of the relay by abusing a specially crafted reset token. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS Schneider Electric reports the following products are affected: Schneider Electric PowerLogic P5: Versions 01.500.104 and prior 3.2 Vulnerability Overview 3.2.1 USE OF A BROKEN OR RISKY CRYPTOGRAPHIC ALGORITHM CWE-327 A vulnerability exists, which could cause denial of service, a device reboot, or an attacker to gain full control of the relay. When a specially-crafted reset token is entered into the front panel of the device, an exploit exists due to the device's utilization of a risky cryptographic algorithm. CVE-2024-5559 has been assig...
View CSAF 1. EXECUTIVE SUMMARY CVSS v3 7.4 ATTENTION: Exploitable remotely Vendor: Hitachi Energy Equipment: RTU500 Scripting Interface Vulnerability: Improper Certificate Validation 2. RISK EVALUATION Successful exploitation of this vulnerability could allow attackers to spoof the identity of the service. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following products of Hitachi Energy are affected: RTU500 Scripting Interface: Version 1.0.1.30 RTU500 Scripting Interface: Version 1.0.2 RTU500 Scripting Interface: Version 1.1.1 RTU500 Scripting Interface: Version 1.2.1 RTU500 Scripting Interface: All versions 3.2 Vulnerability Overview 3.2.1 IMPROPER CERTIFICATE VALIDATION CWE-295 Hitachi Energy is aware of a reported vulnerability in the RTU500 Scripting interface. When a client connects to a server using TLS, the server presents a certificate. This certificate links a public key to the identity of the service and is signed by a certification authority (CA), allowing the client to va...
View CSAF 1. EXECUTIVE SUMMARY CVSS v3 8.1 ATTENTION: Exploitable remotely Vendor: Schneider Electric Equipment: EcoStruxure Control Expert, EcoStruxure Process Expert and Modicon M340, M580 and M580 Safety PLCs Vulnerabilities: Improper Enforcement of Message Integrity During Transmission in a Communication Channel, Use of Hard-coded Credentials, Insufficiently Protected Credentials 2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow a denial of service, a loss of confidentiality, and threaten the integrity of controllers. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following Schneider Electric products are affected: Modicon M340 CPU (part numbers BMXP34*): Versions prior to sv3.60 (CVE-2023-6408) Modicon M580 CPU (part numbers BMEP* and BMEH* excluding M580 CPU Safety): Versions prior to SV4.20 (CVE-2023-6408) Modicon M580 CPU Safety: Versions prior to SV4.21 (CVE-2023-6408) EcoStruxure Control Expert: Versions prior to v16.0 EcoStruxure Process Expert:...
View CSAF 1. EXECUTIVE SUMMARY CVSS v3 9.9 ATTENTION: Exploitable remotely/low attack complexity Vendor: Hitachi Energy Equipment: MicroSCADA Pro/X SYS600 Vulnerabilities: Improper Neutralization of Special Elements in Data Query Logic, Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal'), Authentication Bypass by Capture-replay, Missing Authentication for Critical Function, URL Redirection to Untrusted Site ('Open Redirect') 2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow an attacker to inject code towards persistent data, manipulate the file system, hijack a session, or engage in phishing attempts against users. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following Hitachi Energy products are affected: Hitachi Energy MicroSCADA Pro/X SYS600: Version 10.0 to Version 10.5 (CVE-2024-4872, CVE-2024-3980, CVE-2024-3982, CVE-2024-7941) Hitachi Energy MicroSCADA Pro/X SYS600: Version 10.2 to Version 10.5 (CVE-2024-7940) Hitachi En...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 5.1 ATTENTION: Low attack complexity Vendor: CODESYS GmbH Equipment: OSCAT Basic Library Vulnerability: Out-of-bounds Read 2. RISK EVALUATION Successful exploitation of this vulnerability allows an local, unprivileged attacker to access limited internal data of the PLC, which may lead to a crash of the affected service. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions CODESYS OSCAT, are affected: CODESYS OSCAT Basic Library: Version 3.3.5.0 oscat.de OSCAT Basic Library: Versions 3.3.5 and prior oscat.de OSCAT Basic Library: Versions 335 and prior 3.2 Vulnerability Overview 3.2.1 OUT-OF-BOUNDS READ CWE-125 The affected product is vulnerable to an out-of-bounds read in the OSCAT Basic Library, which allows a local, unprivileged attacker to access limited internal data of the PLC which may lead to a crash of the affected service. CVE-2024-6876 has been assigned to this vulnerability. A CVSS v3.1 base score of 5.1 has been calculated;...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 10.0 ATTENTION: Exploitable remotely/low attack complexity Vendor: Automated Logic Equipment: WebCTRL Premium Server Vulnerabilities: Unrestricted Upload of File with Dangerous Type, URL Redirection to Untrusted Site ('Open Redirect') 2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow an unauthenticated remote attacker to execute arbitrary commands on the server hosting WebCTRL or redirect legitimate users to malicious sites. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following Automated Logic products are affected: Automated Logic WebCTRL® Server : Version 7.0 Carrier i-Vu: Version 7.0 Automated Logic SiteScan Web: Version 7.0 Automated Logic WebCTRL for OEMs: Version 7.0 3.2 Vulnerability Overview 3.2.1 UNRESTRICTED UPLOAD OF FILE WITH DANGEROUS TYPE CWE-434 A vulnerability in Automated Logic WebCTRL 7.0 allows an unauthenticated user to upload files of dangerous types without restrictions, which could lead to re...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 7.7 ATTENTION: Exploitable remotely Vendor: Schneider Electric Equipment: Modicon M340, MC80, and Momentum Unity M1E Vulnerabilities: Improper Enforcement of Message Integrity During Transmission in a Communication Channel, Authentication Bypass by Spoofing 2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow an attacker to retrieve password hashes or cause a denial-of-service condition. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Schneider Electric Modicon M340, MC80, and Momentum Unity M1E are affected: Modicon M340 CPU (part numbers BMXP34*): All versions (CVE-2024-8933) Modicon M340 CPU (part numbers BMXP34*): versions after SV3.60 (CVE-2024-8935) Modicon MC80 (part numbers BMKC80): All versions (CVE-2024-8933) Modicon Momentum Unity M1E Processor (171CBU*): All versions (CVE-2024-8933) 3.2 Vulnerability Overview 3.2.1 Improper Enforcement of Message Integrity During Transmission in a Communi...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 9.2 ATTENTION: Exploitable remotely Vendor: Schneider Electric Equipment: Modicon M340, MC80, and Momentum Unity M1E Vulnerabilities: Improper Input Validation, Improper Restriction of Operations within the Bounds of a Memory Buffer 2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow an attacker to tamper with memory on these devices. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Schneider Electric Modicon M340, MC80, and Momentum Unity M1E are affected: Modicon M340 CPU (part numbers BMXP34*): Versions prior to SV3.65 Modicon MC80 (part numbers BMKC80)(CVE-2024-8937, CVE-2024-8938): All versions Modicon Momentum Unity M1E Processor (171CBU*)(CVE-2024-8937, CVE-2024-8938): All versions 3.2 Vulnerability Overview 3.2.1 Improper Input Validation CWE-20 An Input Validation vulnerability exists that could lead to loss of confidentiality of controller memory after a successful Man-In-The-Middle attack ...